This block outputs alarms of series fan-powered terminal unit with constant volume fan. The implementation is according to the Section 5.9.6 of ASHRAE Guideline 36, May 2020.
staTim, if the measured airflow VPri_flow
is less than 70% of setpoint VActSet_flow for 5
minutes (lowFloTim) while the setpoint is greater than
zero, generate a Level 3 alarm.staTim, if the measured airflow VPri_flow
is less than 50% of setpoint VActSet_flow for 5
minutes (lowFloTim) while the setpoint is greater than
zero, generate a Level 2 alarm.staPreMul)
of 0 for its static pressure reset Trim-Respond control loop, low
airflow alarms shall be suppressed for that zone.u1HotPla=true), and the discharge temperature
(TDis) is 8.3 °C (15 °F) less than the setpoint
(TDisSet) for 10 minuts (lowTemTim),
generate a Level 3 alarm.u1HotPla=true), and the discharge temperature
(TDis) is 17 °C (30 °F) less than the setpoint
(TDisSet) for 10 minuts (lowTemTim),
generate a Level 2 alarm.hotWatRes)
of 0 for its hot-water reset Trim-Respond control loop, low
discharing air temperature alarms shall be suppressed for that
zone.Fan alarm is indicated by the status input being different from the output command after a period of 15 seconds after a change in output status.
u1FanCom=true), status off
(u1TerFan=false), generate Level 2 alarm.u1FanCom=false), status on
(u1TerFan=true), generate Level 4 alarm.If the fan serving the zone has been OFF
(u1Fan=false) for 10 minutes (fanOffTim),
and airflow sensor reading VPri_flow is above 10% of
the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
If the damper position (uDam) is 0% and airflow
sensor reading VPri_flow is above 10% of the cooling
maximum airflow setpoint VCooMax_flow for 10 minutes
(leaFloTim) while the fan serving the zone is proven
on (u1Fan=true), generate a Level 4 alarm.
If the valve position (uVal) is 0% for 15 minutes
(valCloTim), discharing air temperature
TDis is above AHU supply temperature TSup
by 3 °C (5 °F), and the fan serving the zone is proven on
(u1Fan=true), gemerate a Level 4 alarm.
Logical.And3 based on ASHRAE
231P, replaced it with a stack of two Logical.And
blocks. This is for #2465.staTim to allow the system becoming
stabilized. This is for issue
3257.