This sequence sets the fan status, damper and valve position for constant-volume series fan-powered terminal unit. The implementation is according to Section 5.9.5 of ASHRAE Guideline 36, May 2020. The calculation is done following the steps below.
uCoo > 0), then the cooling loop output
uCoo shall be mapped to the airflow
setpoint from the minimum VActMin_flow to the cooling maximum
VActCooMax_flow airflow setpoints.
The heating coil is disabled (yVal=0).
TSup from the AHU is greater than
room temperature TZon, cooling supply airflow setpoint shall be
no higher than the minimum.
uCoo=0 and uHea=0), then
the active airflow setpoint shall be the minimum airflow setpoint VActMin_flow.
The heating coil is disabled (yVal=0).
uHea > 0),
uHea increases from 0% to 100%, it shall reset
the discharge temperature THeaDisSet from the current AHU setpoint
temperature TSupSet to a maximum of dTDisZonSetMax
above space temperature setpoint.
VActMin_flow.
u1Fan=true) for a fixed time delay (15 seconds), the damper
override is released.
The sequences of controlling fan, damper position for constant-volume series fan-powered terminal unit are described in the following figure below.
As specified in Section 5.9.7 of ASHRAE Guideline 36, the airflow setpoint could be override by providing software switches that interlock to a system-level point to:
oveFloSet equals to 1, force the zone airflow setpoint
VPri_flow_Set to zero,
oveFloSet equals to 2, force the zone airflow setpoint
VPri_flow_Set to zone cooling maximum airflow rate
VCooMax_flow,
oveFloSet equals to 3, force the zone airflow setpoint
VPri_flow_Set to zone minimum airflow setpoint
VMin_flow.
have_preIndDam to exclude the option of using pressure independant damper.