This block outputs zone alarms. The implementation is according to the ASHRAE Guideline 36, Section 5.3.6.
TZon
is 2 °C (3 °F) above the cooling
setpoint TCooSet
for 10 minutes (timChe
),
generate Level 3 alarm.
TZon
is 3 °C (5 °F) above the cooling
setpoint TCooSet
for 10 minutes (timChe
),
generate Level 2 alarm.
TZon
is 2 °C (3 °F) below the heating
setpoint THeaSet
for 10 minutes (timChe
),
generate Level 3 alarm.
TZon
is 3 °C (5 °F) below the heating
setpoint THeaSet
for 10 minutes (timChe
),
generate Level 2 alarm.
uResSet=true
.
ppmCO2
is less than 300 ppm, or the zone is
in unoccupied mode for more than 2 hours (modChe
) and zone CO2
concentration exceeds 600 ppm, generate a Level 3 alarm. The alarm text shall
identify the sensor and indicate that it may be out of calibration.
CO2Set
) plus 10% for more
than 10 minutes (timChe
), generate a Level 2 alarm.