This block outputs zone alarms. The implementation is according to the ASHRAE Guideline 36, Section 5.3.6.
TZon is 2 °C (3 °F) above
the cooling setpoint TCooSet for 10 minutes
(timChe), generate Level 3 alarm.TZon is 3 °C (5 °F) above
the cooling setpoint TCooSet for 10 minutes
(timChe), generate Level 2 alarm.TZon is 2 °C (3 °F) below
the heating setpoint THeaSet for 10 minutes
(timChe), generate Level 3 alarm.TZon is 3 °C (5 °F) below
the heating setpoint THeaSet for 10 minutes
(timChe), generate Level 2 alarm.uResSet=true.ppmCO2 is less than 300
ppm, or the zone is in unoccupied mode for more than 2 hours
(modChe) and zone CO2 concentration exceeds 600 ppm,
generate a Level 3 alarm. The alarm text shall identify the sensor
and indicate that it may be out of calibration.CO2Set)
plus 10% for more than 10 minutes (timChe), generate a
Level 2 alarm.