.Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection

Information

Enumeration to define how minimum outdoor air and economizer function being designed in multizone AHU. Possible values are:

Enumeration Description
DedicatedDampersAirflow Separate dampers for ventilation and economizer, with airflow measurement station.
DedicatedDampersPressure Separate dampers for ventilation and economizer, with differential pressure sensor.
SingleDamper Single damper for ventilation and economizer, with airflow measurement station.

Definition

type OutdoorAirSection = enumeration(DedicatedDampersAirflow "Separate dampers for ventilation and economizer, with airflow measurement station", DedicatedDampersPressure "Separate dampers for ventilation and economizer, with differential pressure sensor", SingleDamper "Single damper for ventilation and economizer, with airflow measurement station");

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos