.Buildings.Controls.OBC.CDL.Reals.Greater

Information

Block that outputs true if the Real input u1 is greater than the Real input u2, optionally within a hysteresis h.

The parameter h ≥ 0 is used to specify a hysteresis. For any h ≥ 0, the output switches to true if u1 > u2, and it switches to false if u1 ≤ u2 - h. Note that in the special case of h = 0, this produces the output y=u1 > u2.

To disable hysteresis, set h=0.

Usage

Enabling hysteresis can avoid frequent switching.
In simulation, adding hysteresis is recommended to guard against numerical noise. Otherwise, numerical noise from a nonlinear solver or from an implicit time integration algorithm may cause the simulation to stall. Numerical noise can be present if an input depends on a state variable or a quantity that requires an iterative solution, such as a temperature or a mass flow rate of an HVAC system.
In real controllers, adding hysteresis is recommended to guard against measurement noise. Otherwise, measurement noise may cause the output to change frequently.