This model validates Buildings.DHC.ETS.BaseClasses.CollectorDistributor in a configuration where the model is used to connect
m_flow_nominal and two active secondary circuits,
one with a mass flow rate varying from 0.5 to 1 times
m_flow_nominal,
another with a constant mass flow rate, equal to 0.5 times
m_flow_nominal: this case illustrates a typical supply-through
loop and the supply temperature drop in one secondary circuit resulting
from flow recirculation when the sum of the secondary mass flow rates
exceeds the primary mass flow rate;
m_flow_nominal (similar to the previous case) and
two passive secondary circuits, with no recirculation loop at the
end of the distribution line,
| Name | Description | 
|---|---|
| Source side medium |