.Buildings.DHC.ETS.BaseClasses.Validation.CollectorDistributor

Information

This model validates Buildings.DHC.ETS.BaseClasses.CollectorDistributor in a configuration where the model is used to connect

  1. an active primary circuit which mass flow rate varies from 0 to 1.1 times m_flow_nominal and two active secondary circuits, one with a mass flow rate varying from 0.5 to 1 times m_flow_nominal, another with a constant mass flow rate, equal to 0.5 times m_flow_nominal: this case illustrates a typical supply-through loop and the supply temperature drop in one secondary circuit resulting from flow recirculation when the sum of the secondary mass flow rates exceeds the primary mass flow rate;
  2. an active primary circuit which mass flow rate varies from 0 to 1.1 times m_flow_nominal (similar to the previous case) and two passive secondary circuits, with no recirculation loop at the end of the distribution line,
  3. a passive primary circuit and two active secondary circuits, both with a varying mass flow rate, with no recirculation loop at the end of the distribution line.

Contents

NameDescription
 MediumSource side medium

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos