Chiller controller
This is a controller for the chiller system, which includes the
dedicated condenser and evaporator pumps.
The system is enabled if any of the input control signals
uHea or uCoo is true. When
enabled,
- the condenser and evaporator pumps are operated at constant
speed, and
- the condenser (resp. evaporator) mixing valve is modulated with
a PI loop controlling the minimum (resp. maximum) inlet
temperature.
- July 31, 2020, by Antoine Gautier:
First implementation.