Chiller controller
This is a controller for the chiller system, which includes the dedicated
condenser and evaporator pumps.
The system is enabled if any of the input control signals uHea
or uCoo
is true
.
When enabled,
-
the condenser and evaporator pumps are operated at constant speed, and
-
the condenser (resp. evaporator) mixing valve is modulated with a PI
loop controlling the minimum (resp. maximum) inlet temperature.
-
July 31, 2020, by Antoine Gautier:
First implementation.