This block implements the control logic for the district heat exchanger, which realizes the interface between the building system and the district system.
The input signal u
is yielded by the supervisory controller, see
Buildings.DHC.ETS.Combined.Controls.Supervisory.
The primary and secondary circuits are enabled to operate if this input signal
is greater than zero and the return position of at least one isolation valve
is greater than 90%.
When enabled,
u
,
which is mapped to modulate in sequence the mixing valve
(from full bypass to closed bypass for a control signal varying between
0% and 30%) and the pump speed (from the minimum to the maximum value
for a control signal varying between 30% and 100%),
u
.
Note that the valve on the secondary side is needed to stabilize the control of the system when the secondary mass flow rate required to meet the heat or cold rejection demand is below the flow rate corresponding to the minimum pump speed.