This is an update of
Buildings.Controls.OBC.CDL.Reals.PIDWithReset
with an additional Boolean input representing an enable signal.
-
When enabled, the controller output is identical to
Buildings.Controls.OBC.CDL.Reals.PIDWithReset
(and the controller integral term is reset to
yMin
at
enabling time).
-
When disabled, the controller output is zero (and the set point
is replaced by the measurement signal to avoid any
time integration of the control error).