This block implements an ideal control of the evaporator (or
condenser) water mass flow rate. The control intent aims to
maintain a constant water temperature difference
dT_nominal across the heat exchanger, within the limit
of a minimum mass flow rate ratio ratFloMin. For
computational performance and to avoid the use of a PI controller,
the required mass flow rate is computed based on a signal
representative of the load.