.Buildings.DHC.ETS.Combined.Controls.PrimaryVariableFlow

Ideal control of condenser or evaporator variable flow rate

Information

This block implements an ideal control of the evaporator (or condenser) water mass flow rate. The control intent aims to maintain a constant water temperature difference dT_nominal across the heat exchanger, within the limit of a minimum mass flow rate ratio ratFloMin. For computational performance and to avoid the use of a PI controller, the required mass flow rate is computed based on a signal representative of the load.

Revisions