This block implements the supervisory reset of the heating water
supply temperature. The heating water supply temperature is reset
down whenever the heating demand signal yielded by the building
automation system is false. This enables operating the
chiller at a reduced lift whenever there is no requirement on the
water temperature supplied to the building system.
Note that the chilled water supply temperature is not reset for the sake of simplicity. It would indeed require a more involved algorithm preventing the reset in case it limits the cold rejection capacity considering the actual district water temperature.