Supervisory controller
This block implements the supervisory control functions of the ETS model
Buildings.DHC.ETS.Combined.ChillerBorefield.
-
Heating (resp. cooling) is enabled based on the input signal
uHea
(resp. uCoo
) which is held for 15', meaning that,
when enabled, the mode remains active for at least 15 minutes and,
when disabled, the mode cannot be enabled again for at least 15 minutes.
The heating and cooling enable signals should be computed externally based on a schedule
(to lock out the system during off-hours), ideally in conjunction with the number
of requests yielded by the terminal unit controllers, or any
other signal representative of the load.
Indeed, the heating water supply set point is allowed to be reset down
only when heating is disabled, in which
case the system performance is improved due to a lower chiller lift.
-
The controller resets the heating water supply temperature based on the logic described in
Buildings.DHC.ETS.Combined.Controls.Reset.
Note that this resetting logic is meant to operate the chiller at low lift.
The chilled water supply temperature may be also reset down by
Buildings.DHC.ETS.Combined.Controls.SideCold
to maintain the heating water supply temperature set point.
This second resetting logic is required for the heating function of the unit,
but it has a negative impact on the lift.
-
Eventually the systems serving as ambient sources are controlled based on the
maximum of the control signals
yAmb
yielded by
Buildings.DHC.ETS.Combined.Controls.SideHot
and
Buildings.DHC.ETS.Combined.Controls.SideCold.
-
March 6, 2025, by Hongxiang Fu:
-
Added reset to the chilled water set point.
-
Added
uCoo
as an additional input
to conHot
.
These are for
#4133.
-
July 31, 2020, by Antoine Gautier:
First implementation.