This block implements the supervisory control functions of the ETS model Buildings.DHC.ETS.Combined.ChillerBorefield.
uHea
(resp. uCoo
) which is held for 15', meaning that,
when enabled, the mode remains active for at least 15 minutes and,
when disabled, the mode cannot be enabled again for at least 15 minutes.
The heating and cooling enable signals should be computed externally based on a schedule
(to lock out the system during off-hours), ideally in conjunction with the number
of requests yielded by the terminal unit controllers, or any
other signal representative of the load.
Indeed, the heating water supply set point is allowed to be reset down
only when heating is disabled, in which
case the system performance is improved due to a lower chiller lift.
yAmb
yielded by
Buildings.DHC.ETS.Combined.Controls.SideHot
and
Buildings.DHC.ETS.Combined.Controls.SideCold.