This model uses the base energy transfer station defined in Buildings.DHC.ETS.Combined.BaseClasses.PartialHeatPumpHeatExchanger.
Domestic hot water is produced using a dedicated water-to-water heat pump with storage tank.
Heating is enabled based on the input signal uSHW
which is held for 15 minutes, meaning that,
when enabled, the mode remains active for at least 15 minutes and,
when disabled, the mode cannot be enabled again for at least 15 minutes.
The enable signal should be computed externally based
on a schedule (to lock out the system during off-hours), ideally in conjunction
with the number of requests or any other signal representative of the load.
When enabled,
QReqHotWat_flow
) combined with the operation of a thermostatic
mixing valve used to mix down the temperature of hot water leaving the domestic hot water heat exchanger
to the temperature distributed to fixtures (parameter THotWatSup_nominal
)
using domestic cold water at the cold water temperature (input TColWat
).
The desired water flow rate leaving the thermostatic mixing valve
is determined according to the following equation:
QReqHotWat_flow
= ṁ cp (THotWatSup_nominal
- TColWat
)