Partial base class for subsystems containing a heat pump
This model represents a water-to-water heat pump, as described
in Buildings.Fluid.HeatPumps.Carnot_TCon,
the condenser pump, and the evaporator side hydronics and
control.
Evaporator Controls
The system is enabled when the input control signal
uEna switches to true. When enabled,
- the evaporator pump is commanded on and supplies the nominal
mass flow rate,
- a three-way diverging valve is used to bypass flow through the
evaporator and is controlled by a PI controller to maintain
dT_nominal across the district supply and return
flows.
Contents
| Name |
Description |
Medium1 |
Medium model on condenser side |
Medium2 |
Medium model on evaporator side |
- February 15, 2024, by Ettore Zanetti:
Made heat pump model dynamic and added junction.
- November 15, 2023, by David Blum:
Changed to partial base class with evaporator hydronics and
control.
- November 16, 2022, by Michael Wetter:
Set pumEva.dp_nominal to correct value.
- February 23, 2021, by Antoine Gautier:
First implementation.