This model represents a water-to-water heat pump, as described in
Buildings.Fluid.HeatPumps.Carnot_TCon, the condenser pump, and the
evaporator side hydronics and control.
Evaporator Controls
The system is enabled when the input control signal uEna
switches to
true
.
When enabled,
-
the evaporator pump is commanded on and supplies the nominal mass flow rate,
-
a three-way diverging valve is used to bypass flow through the evaporator and
is controlled by a PI controller to maintain
dT_nominal
across
the district supply and return flows.
Contents
Name | Description |
---|
Medium1 | Medium model on condenser side |
Medium2 | Medium model on evaporator side |
-
February 15, 2024, by Ettore Zanetti:
Made heat pump model dynamic and added junction.
-
November 15, 2023, by David Blum:
Changed to partial base class with evaporator hydronics and control.
-
November 16, 2022, by Michael Wetter:
Set pumEva.dp_nominal
to correct value.
-
February 23, 2021, by Antoine Gautier:
First implementation.