.Buildings.DHC.ETS.Combined.Subsystems.Borefield

Information

This is a model for a borefield system with a variable speed pump and a mixing valve modulated to maintain a maximum inlet temperature.

The system is controlled based on the logic described in Buildings.DHC.ETS.Combined.Controls.Borefield. The pump flow rate is considered proportional to the pump speed under the assumption of a constant flow resistance in the borefield loop. This assumption is justified by the connection of the loop to the buffer tanks, and by the additional assumption that the bypass branch of the mixing valve is balanced with the direct branch.

(The parameter from_dp of the valve model is set to false to simplify the system of algebraic equations, which, in this specific case, alleviates non-convergence issues.)

Contents

NameDescription
 BorefieldTypeWall heat transfer