This is a partial model used as a base class to construct the
validation and example models.
-
The building distribution pumps are variable speed and the flow rate
is considered to vary linearly with the load (with no inferior limit).
-
The Boolean enable signals for heating and cooling typically provided
by the building automation system are here computed based on the condition
that the load is greater than 1% of the nominal load.
-
Simplified chiller performance data are used, which represent a linear
variation of the EIR and the capacity with the evaporator outlet temperature
and the condenser inlet temperature (no variation of the EIR at part
load is considered).