Geothermal borefield model
This model represents a borefield composed of 350 boreholes,
with the following main assumptions.
- 
The soil is made of sandstone.
- 
The boreholes are filled with a bentonite grout.
- 
The boreholes have a height of 300 m and a diameter of 190 mm.
They are discretized vertically in five segments.
- 
A distance of 10 m between each borehole is considered.
- 
HDPE pipes with a diameter of 40 mm are considered, in a
double U-tube parallel configuration.
- 
May 17, 2024, by Michael Wetter:
 Updated model due to removal of parameterdynFil.
 This is for
IBPSA, #1885.
- 
January 8, 2024, by David Blum:
 Moved toBuildings.DHC.Examples.Combined.BaseClasses.Borefield.
This is for
issue 3628.
- 
May 31, 2023, by Michael Wetter:
 Removedfinalmodifier forborFieDatto allow record to be replaced
in models that extend this model.
- 
February 23, 2021, by Antoine Gautier:
 Updated documentation.
- 
January 12, 2020, by Michael Wetter:
 Added documentation.
Generated at 2025-10-30T19:21:05Z
 by OpenModelicaOpenModelica 1.25.5 using GenerateDoc.mos