Geothermal borefield model
This model represents a borefield composed of 350 boreholes,
with the following main assumptions.
- The soil is made of sandstone.
- The boreholes are filled with a bentonite grout.
- The boreholes have a height of 300 m and a diameter of 190 mm.
They are discretized vertically in five segments.
- A distance of 10 m between each borehole is considered.
- HDPE pipes with a diameter of 40 mm are considered, in a double
U-tube parallel configuration.
- May 17, 2024, by Michael Wetter:
Updated model due to removal of parameter
dynFil.
This is for IBPSA,
#1885.
- January 8, 2024, by David Blum:
Moved to
Buildings.DHC.Examples.Combined.BaseClasses.Borefield.
This is for issue
3628.
- May 31, 2023, by Michael Wetter:
Removed final modifier for borFieDat to
allow record to be replaced in models that extend this model.
- February 23, 2021, by Antoine Gautier:
Updated documentation.
- January 12, 2020, by Michael Wetter:
Added documentation.
Generated at 2026-04-03T18:18:27Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos