Partial model to be used for modeling
See the schematics below for a description of the physical boundaries of the composing systems.
The parameters defining the set of outside connectors of this class
are propagated up from the ETS and building components.
The connect clauses between the ETS and the building connectors
are automatically generated based on the previous parameters and the
additional parameters nPorts_heaWat
and nPorts_chiWat
that need to be specified.
In case of a heating service line, the model allows for using two
different media at the inlet port_aSerHea
and at the oulet
port_bSerHea
to represent a steam supply and condensate
return.
Scaling is implemented by means of a multiplier factor facMul
.
Each extensive quantity (mass and heat flow rate, electric power)
flowing out through fluid ports, or connected to an
output connector is multiplied by facMul
.
Each extensive quantity (mass and heat flow rate, electric power)
flowing in through fluid ports, or connected to an
input connector is multiplied by 1/facMul
.
This allows modeling, with a single instance,
multiple identical buildings with identical energy transfer stations,
served by the same service line.
Name | Description |
---|---|
MediumSer | Service side medium |
MediumSerHea_a | Service side medium at heating inlet |
MediumBui | Building side medium |
have_pum
to instance
totPPum
for cases where ETS and building both don't have pumping.