.Buildings.DHC.Plants.Combined.Controls.BaseClasses.StageIndex

Information

This block is used to compute the stage index of the plant or of multiple lead/lag units such as pump groups.

At initial time, stage #0 is active. The transition to stage #1 is triggered when stage #0 has been active for the minimum runtime and when either the Enable signal u1 has a rising edge or when the stage up signal u1Up is true.

From stage #i, the transition to stage #i+1 (resp. i-1) is triggered when stage #i has been active for the minimum runtime and when the stage up signal u1Up (resp. stage down signal u1Dow) is true. From stage #i, the transition to stage #0 is triggered when stage #i has been active for the minimum runtime and the Enable signal u1 is false.