This block is used to compute the stage index of the plant or of multiple lead/lag units such as pump groups.
At initial time, stage #0
is active.
The transition to stage #1
is triggered when stage #0
has been active
for the minimum runtime and when either the Enable signal u1
has a rising edge or when the stage up signal u1Up
is true
.
From stage #i
, the transition to stage #i+1
(resp. i-1
) is triggered
when stage #i
has been active for the minimum runtime and when the
stage up signal u1Up
(resp. stage down signal u1Dow
)
is true
.
From stage #i
, the transition to stage #0
is triggered
when stage #i
has been active for the minimum runtime and the Enable signal
u1
is false
.