.Buildings.DHC.Plants.Combined.Controls.BaseClasses.TankCycle

Information

The tank operating conditions should match the operating limits and selection conditions of the chillers and HRCs. The highest temperature (at the top of the tank) should be limited by the maximum evaporator entering temperature per manufacturer’s recommendations. The lowest temperature (at the bottom of the tank) should be limited by the design CHW supply temperature. This gives the tank maximum ΔT and the actual storage capacity. However, this value is likely above the maximum ΔT that chillers and HRCs can achieve across the condenser or evaporator barrel (typically 11 K). Therefore, in order to fully leverage the TES capacity, two temperature cycles are needed.

The first tank cycle (higher temperature setpoint) is activated whenever all of the following conditions are true.

The second tank cycle (lower temperature setpoint) is activated whenever both of the following conditions are true.

At initial time the tank cycle flag is set based on the tank temperature condition only from the above two clauses without a time delay. If neither condition is true, the tank cycle flag is set based on the flow condition only in the above two clauses without a time delay.

The minimum runtime of each tank cycle is fixed at 30 min.