.Buildings.DHC.Plants.Combined.Controls.Controller

Information

This block implements the following control functions.

Heat pumps

Heat pumps are enabled whenever Charge Assist mode is active and any CWC pump is enabled. Heat pumps are disabled otherwise.

The supply temperature setpoint is K plus the highest setpoint of the active tank cycle. Note that no limitation of the setpoint value per HP manufacturer specification is taken into account.

CHW, HW, CWE and CWC pumps

The lead pump is enabled based on the logic described in Buildings.DHC.Plants.Combined.Controls.BaseClasses.ValveCondenserEvaporator.

Pumps are staged based on the logic described in Buildings.DHC.Plants.Combined.Controls.BaseClasses.StagingPump.

When any pump is enabled, the pump speed is modulated by a PI controller tracking a differential pressure setpoint at the boundaries of the circuit served by the pump. The control loop is biased to launch from 100 % (maximum speed). All pumps within the same group receive the same speed command signal.

The differential pressure setpoint for the CHW and HW loops is provided as a control input. Ideally, a reset logic based on consumer valve requests should be implemented to adapt those setpoints to the demand. For the sake of simplicity, the differential pressure setpoint for the CWC and CWE loops is a fixed parameter (design pressure drop).

Revisions


Generated at 2024-11-26T19:26:15Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos