This model implements the chilled water loop bypass valve control logic as follows:
When the plant is on, the PID controller controls the valve opening ratio to reach the scaled mass flow rate setpoint.
The setpoint is mMin_flow
multiplied by the number of chillers
that are on. mMin_flow
is the minimum mass flow rate required by
one chiller.
This control sequence assumes that all the chillers are identical and the cooling load is evenly split between all of the chillers that are on.