.Buildings.DHC.Plants.Cooling.Controls.ChilledWaterBypass

Information

This model implements the chilled water loop bypass valve control logic as follows:

When the plant is on, the PID controller controls the valve opening ratio to reach the scaled mass flow rate setpoint.

The setpoint is mMin_flow multiplied by the number of chillers that are on. mMin_flow is the minimum mass flow rate required by one chiller.

This control sequence assumes that all the chillers are identical and the cooling load is evenly split between all of the chillers that are on.

Revisions