This model simulates parallel connected cooling tower subsystem with a bypass valve.
The bypass valve is controlled to enforce that the leaving condenser water
temperature does not drop below the minimum temperature TMin
.
By default, the condenser water setpoint is the ambient wet bulb temperature
TWetBul
plus the approach temperature dTApp
.
Inside the model, a cooling tower fan speed controller is also implemented to maintain the condenser water at its setpoint.
dp_fixed = 0
for the bypass valve because the pressure drop in this leg
will be significantly less than the cooling towers.riseTime
for the valve signal filters.
use_inputFilter = false
for shut-off valve in cooling tower.
This avoids a sharp rise in pressure near t=35 seconds.