.Buildings.Electrical.AC.ThreePhasesUnbalanced.Validation.IEEETests.Test4NodesFeeder

Information

This package contains examples that shows the validation of the models against the IEEE four-nodes test feeder validation procedure . The tests that are part of the validation certify the capability to represent transformers of various configurations, full three-phase lines, and unbalanced loads.

image

The figure shows the structure of the four-nodes network. The voltage source is connected to the load through two lines and a transformer. The validation procedure consists of mutliple tests in which the type of the load and the type of the transformer vary. The test cases that have been successfully implemented using the models of the Buildings.Electrical package.

Each example in this package is part of the validation tests. The examples have been grouped into sub-packages depending on the characteristics of the validation test. The table below summarizes the examples that are part of this package.

Transformer Load
Gr Y - Gr Y Step Up Balanced
Gr Y - D Step Up Balanced
D - D Step Up Balanced
Gr Y - Gr Y Step Down Balanced
Gr Y - D Step Down Balanced
D - D Step Down Balanced
Gr Y - Gr Y Step Up Unbalanced
Gr Y - D Step Up Unbalanced
D - D Step Up Unbalanced
Gr Y - Gr Y Step Down Unbalanced
Gr Y - D Step Down Unbalanced
D - D Step Down Unbalanced

For example Gr Y - D Step Up indicates that the transformer has a grounded Y connection at the primary side, and a D connection at the secondary side. Step up indicates that the voltage at the secondary side is higher than the primary side. Each test listed in the table produces results that differ from the reference IEEE values by less than 0.05%, which is the threshold defined by IEEE to determine whether results should be accepted or not.

References

Kersting, William H.
Radial distribution test feeders
Power Engineering Society Winter Meeting (2) p. 908-912, 2001. IEEE

Contents

NameDescription
 BalancedStepDownPackage that contains the examples for balanced loads and step down transformer
 BalancedStepUpPackage that contains the examples for balanced loads and step up transformer
 UnbalancedStepDownPackage that contains the examples for unbalanced loads and step down transformer
 UnbalancedStepUpPackage that contains the examples for unbalanced loads and step up transformer
 BaseClassesThis package contains the base classes used by the IEEE 4 nodes test feeder