Block that is applied for multizone VAV AHU control. It outputs the supply fan status and the operation speed, outdoor and return air damper position, supply air temperature setpoint and the valve position of the cooling and heating coils. It is implemented according to the ASHRAE Guideline 36, PART 5.N.
The sequence consists of five subsequences.
The fan speed control is implemented according to PART 5.N.1. It outputs
the boolean signal ySupFan
to turn on or off the supply fan.
In addition, based on the pressure reset request uZonPreResReq
from the VAV zones controller, the
sequence resets the duct pressure setpoint, and uses this setpoint
to modulate the fan speed ySupFanSpe
using a PI controller.
See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.SupplyFan
for more detailed description.
According to current occupany, supply operation status ySupFan
,
zone temperatures and the discharge air temperature, the sequence computes the
minimum outdoor airflow rate setpoint, which is used as input for the economizer control.
More detailed information can be found in
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.
The block outputs outdoor and return air damper position, yOutDamPos
and
yRetDamPos
. First, it computes the position limits to satisfy the minimum
outdoor airflow requirement. Second, it determines the availability of the economizer based
on the outdoor condition. The dampers are modulated to track the supply air temperature
loop signal, which is calculated from the sequence below, subject to the minimum outdoor airflow
requirement and economizer availability. Optionally, there is also an override for freeze protection.
See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Controller
for more detailed description.
Based on PART 5.N.2, the sequence first sets the maximum supply air temperature
based on reset requests collected from each zone uZonTemResReq
. The
outdoor temperature TOut
and operation mode uOpeMod
are used
along with the maximum supply air temperature, for computing the supply air temperature
setpoint. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.SupplyTemperature
for more detailed description.
The subsequence retrieves supply air temperature setpoint from previous sequence. Along with the measured supply air temperature and the supply fan status, it generates coil valve positions. See Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.SupplySignals
0
to 0.0
and 1
to 1.0
.