.Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulation

Information

This is a multi zone VAV AHU economizer modulation block. It calculates the outdoor and return air damper positions based on the supply air temperature control loop signal. The implementation is in line with ASHRAE Guidline 36 (G36), PART 5.N.2.c. Damper positions are linearly mapped to the supply air control loop signal. This is a final sequence in the composite multi zone VAV AHU economizer control sequence. Damper position limits, which are the inputs to the sequence, are the outputs of Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits and Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Enable sequences.

When the economizer is enabled, the PI controller modulates the damper positions. Return and outdoor damper are not interlocked. When the economizer is disabled, the damper positions are set to the minimum outdoor air damper position limits.

The control charts below show the input-output structure and an economizer damper modulation sequence assuming a well configured controller. Control diagram:

Image of the multi zone AHU modulation sequence control diagram

Multi zone AHU economizer modulation control chart:

Image of the multi zone AHU modulation sequence expected performance

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos