modelOutdoorAirFlow
Validate the sequences of setting AHU level minimum outdoor airflow rate
Information
This model shows how to compose the subsequences to find the minimum outdoor airflow setpoint of an AHU unit that serves three zones.
-
The blocks
zon1,zon2andzon3which instantiate Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Zone, calculate the zone level minimum outdoor airflow setpoints. -
The block
zonToAhuwhich instantiates Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.SumZone, finds the sum, minimum and maximum of the zone level setpoints. -
The AHU level minimum outdoor airflow setpoint is then specified by block
ahu1. See Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.AHU.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Zone | zon1 | Outdoor airflow related calculations for zone 1 | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Zone | zon2 | Outdoor airflow related calculations for zone 2 | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Zone | zon3 | Outdoor airflow related calculations for zone 3 | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.AHU | ahu1 | AHU level minimum outdoor airflow setpoint | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.SumZone | zonToAhu | From zone level to AHU level |
Revisions
-
March 14, 2020, by Jianjun Hu:
First implementation.