This sequence conducts calculations of the minimum outdoor airflow rate at the zone level. It gives outputs below.
VDesPopBreZon_flow.
VDesAreBreZon_flow.
yDesPriOutAirFra.
VUncOutAir_flow. This flow rate
is calculated based on: occupancy (if there is occupancy sensor) or design
occupancy (if there is no occupancy sensor), and air distribution effectiveness
(warm or cool air).
yPriOutAirFra.
VPriAir_flow.
The calculation is done using the steps below.
Compute the required breathing zone outdoor airflow using the following components.
VDesAreBreZon_flow.
VDesPopBreZon_flow.
The number of occupant in the zone can be retrieved directly from occupancy sensor
(nOcc) if the sensor exists, or using the default occupant density
(occDen) and multiplying it with zone area (AFlo).
The occupant density can be found from Table 6.2.2.1 in ASHRAE Standard
62.1-2013. For design purpose, use the design zone population (desZonPop)
to determine the minimum requirement at the ventilation-design condition.
Compute the zone air-distribution effectiveness.
Table 6.2.2.2 in ASHRAE 62.1-2013 lists some typical values for setting the
effectiveness. Depending on difference between zone space temperature
TZon and discharge air temperature (after the reheat coil) TDis, Warm-air
effectiveness zonDisEffHea or Cool-air effectiveness
zonDisEffCoo should be applied.
Compute the required zone outdoor airflow zonOutAirRate.
If the zone is in any mode other than occupied mode (uReqOutAir=false)
or if the zone has window switches and the window is open (uWin=true),
set zonOutAirRate = 0.
Otherwise, the required zone outdoor airflow zonOutAirRate
shall be calculated as follows:
nOcc > 0), or if there is no occupancy sensor
(have_occSen = false):
zonOutAirRate = (breZonAre+breZonPop)/disEffCoo.
zonOutAirRate = (breZonAre+breZonPop)/disEffHea.
nOcc=0):
zonOutAirRate = breZonAre/disEffCoo.
zonOutAirRate = breZonAre/disEffHea.
Compute the outdoor air fraction for the zone yPriOutAirFra as follows.
Set the zone outdoor air fraction to
yPriOutAirFra = zonOutAirRate/VPriAir_flow
where, VPriAir_flow is the maximum between the measured discharge air
flow rate from the zone VAV box VDis_flow and 0.1% of AHU level
design uncorrected minimum outdoor airflow rate VUncOut_flow_nominal.
For design purpose, the design zone outdoor air fraction yDesPriOutAirFra
is
yDesPriOutAirFra = desZonOutAirRate/minZonPriFlo
where minZonPriFlo is the minimum expected zone primary flow rate and
desZonOutAirRate is the required design zone outdoor airflow rate.
ANSI/ASHRAE Standard 62.1-2013, Ventilation for Acceptable Indoor Air Quality.
Stanke, D., 2010. Dynamic Reset for Multiple-Zone Systems. ASHRAE Journal, March 2010.
min attribute of desZonPop to zero, and used
the expression as a default value. This was done because the expression involves the
zone floor area, which is, if obtained from Spawn, a non-literal value.
fill when assigning the unit attribute.each.
cooCtrlSig input with TZon and TDis
inputs to check if cool or warm air distribution effectiveness should be applied.
Applied hysteresis to avoid rapid change.