.Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.SingleZone.VAV.SetPoints.OutsideAirFlow

Information

This atomic sequence sets the minimum outdoor airflow setpoint for compliance with the ventilation rate procedure of ASHRAE 62.1-2013. The implementation is according to ASHRAE Guidline 36 (G36), PART 5.P.4.b, PART 5.B.2.b, PART3.1-D.2.a.

Step 1: Minimum breathing zone outdoor airflow required breZon

The number of occupant occCou could be retrieved directly from occupancy sensor nOcc if the sensor exists (have_occSen=true), or using the default occupant density occDen to find it AFlo*occDen. The occupant density can be found from Table 6.2.2.1 in ASHRAE Standard 62.1-2013.

Step 2: Zone air-distribution effectiveness zonDisEff

Table 6.2.2.2 in ASHRAE 62.1-2013 lists some typical values for setting the effectiveness. Depending on difference between zone space temperature TZon and supply air temperature TDis, Warm-air effectiveness zonDisEffHea or Cool-air effectiveness zonDisEffCoo should be applied.

Step 3: Minimum required zone outdoor airflow zonOutAirRate

For each zone in any mode other than occupied mode and for zones that have window switches and the window is open, zonOutAirRate shall be zero. Otherwise, the required zone outdoor airflow zonOutAirRate shall be calculated as follows:

If the zone is populated, or if there is no occupancy sensor: If the zone has an occupancy sensor and is unpopulated:

For the single zone system, the required minimum outdoor airflow setpoint VOutMinSet_flow equals to the zonOutAirRate.

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos