This sequence sums up the zone level status calculation to find the outputs that are needed to define the zone group operation mode.
It requires following inputs from zone level controller:
zonOcc
: if the zone-level local override switch indicates the zone is
occupied,
uOcc
: if the zone is occupied according to its occupancy schedule,
tNexOcc
: time to next occupied period,
uCooTim
: required cooldown time,
uWarTim
: required warm-up time,
uOccHeaHig
: if the zone temperature is lower than the occupied
heating setpoint,
uHigOccCoo
: if the zone temperature is higher than the occupied
cooling setpoint,
uUnoHeaHig
: if the zone temperature is lower than the unoccupied
heating setpoint,
THeaSetOff
: zone unoccupied heating setpoint,
uEndSetBac
: if the zone could end the setback mode,
uHigUnoCoo
: if the zone temperature is higher than its unoccupied
cooling setpoint,
TCooSetOff
: zone unoccupied cooling setpoint,
uEndSetUp
: if the zone could end the setup mode,
TZon
: zone temperature,
uWin
: True when the window is open, false when the window is close
or the zone does not have window status sensor.
The sequence gives following outputs for zone group level calculation:
uGroOcc
: the zone group should be in occupied mode when there is any
zone becoming occupied according its schedule or due to the local override,
nexOcc
: the shortest time to the next occupied period among all the
zones in the group,
yCooTim
: longest cooldown time,
yWarTim
: longest warm-up time,
yOccHeaHig
: if there is zone with temperature being lower than the
occupied heating setpoint, so the group could be in the warm-up mode,
yHigOccCoo
: if there is zone with temperature being higher than the
occupied cooling setpoint, so the group could be in the cooldown mode,
yColZon
: total number of zones that the temperature is lower than the
unoccupied heating setpoint,
ySetBac
: check if the group could be into setback mode due to that
the average zone temperature is lower than the average unoccupied heating setpoint,
yEndSetBac
: check if the group should end setback mode due to that
all the zone temperature are above their unoccupied heating setpoint by a limited
value,
yHotZon
: total number of zones that the temperature is higher than the
unoccupied cooling setpoint,
ySetUp
: check if the group could be into setup mode due to that
the average zone temperature is higher than the average unoccupied cooling setpoint,
yEndSetUp
: check if the group should end setup mode due to that
all the zone temperature are below their unoccupied cooling setpoint by a limited
value,
TZonMax
: maximum zone temperature in the zone group,
TZonMin
: minimum zone temperature in the zone group,
yOpeWin
: total number of opening windows.