.Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.DamperValves

Information

This sequence sets the damper and valve position for VAV reheat terminal unit. The implementation is according to ASHRAE Guideline 36 (G36), PART 5.E.6. The calculation is done following the steps below.

  1. When the zone state is cooling (uCoo>0), then the cooling loop output uCoo shall be mapped to the airflow setpoint from the cooling minimum VActCooMin_flow to the cooling maximum VActCooMax_flow airflow setpoints. The hot water valve is closed (yHeaVal=0) unless the discharge air temperature TDis is below the minimum setpoint (10 °C).

  2. If supply air temperature TSup from the AHU is greater than room temperature TZon, cooling supply airflow setpoint shall be no higher than the minimum.

  3. When the zone state is Deadband (uCoo=0 and uHea=0), then the active airflow setpoint shall be the minimum airflow setpoint VActMin_flow. Hot water valve is closed unless the discharge air temperature is below the minimum setpoint (10 °C).

  4. When the zone state is Heating (uHea>0), then the heating loop shall maintain space temperature at the heating setpoint as follows:

  5. The hot water valve (or modulating electric heating coil) shall be modulated to maintain the discharge temperature at setpoint.

  6. The VAV damper shall be modulated by a control loop to maintain the measured airflow at the active setpoint.

The sequences of controlling damper and valve position for VAV reheat terminal unit are described in the following figure below.

Image of damper and valve control for VAV reheat terminal unit

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos