This atomic sequence sets the active maximum and minimum setpoints VActCooMax_flow, VActCooMin_flow, VActMin_flow, VActHeaMin_flow, VActHeaMax_flow for VAV reheat terminal unit according to ASHRAE Guideline 36 (G36), PART 5.E.3-5.

1. Information provided by designer

According to G36 PART 3.1.B.2, following VAV box design information should be provided:

2. Occupied minimum airflow VOccDisMin_flow

The VOccDisMin_flow shall be equal to zone minimum airflow setpoint VDisSetMin_flow except as follows:

3. Active maximum and minimum setpoints

The setpoints shall vary depending on the mode of the zone group.

Setpoint OccupiedCool-down SetupWarmupSetbackUnoccupied
Cooling maximum (VActCooMax_flow)VDisCooSetMax_flow VDisCooSetMax_flowVDisCooSetMax_flow 000
Cooling minimum (VActCooMin_flow)VOccDisMin_flow 00000
Minimum (VActMin_flow)VOccDisMin_flow0 0000
Heating minimum (VActHeaMin_flow)VOccDisMin_flow 00VDisHeaSetMax_flowVDisHeaSetMax_flow 0
Heating maximum (VActHeaMax_flow)max(VDisHeaSetMax_flow,VOccDisMin_flow) VDisHeaSetMax_flow0VDisCooSetMax_flowVDisCooSetMax_flow 0