Validation test for the block Buildings.Obsolete.Controls.OBC.CDL.Continuous.LimPID.
This model validates setting the initial state of the controller to a specified value.
The model sets the initial values xi_start=0.25
of the integrator for both instances of the controller.
For the instance limPID
, it also sets the initial value of the state of the
derivative block xd_start=-0.5
.
The derivative block obtains as an input signal the value
u=-0.5 because the set point weight for the derivative action is wd=0
.
Therefore, an initial state of x(t0)=-0.5 causes the state of the derivative
block to be at steady-state, because
dx(t)/dt = (u - x)/T.