The minimum flow bypass valve is modulated based on a reverse acting control loop to maintain the primary flow rate at setpoint. The setpoint is calculated as described in Buildings.Templates.Plants.Controls.MinimumFlow.Setpoint.
When using isolation valve command signals
(have_valInlIso=true
or have_valOutIso=true
):
When any valve is commanded open, the bypass valve control loop is enabled.
The valve is opened 100 % otherwise.
When enabled, the bypass valve loop shall be biased to start with the valve 100 % open.
Otherwise
(have_valInlIso=false
and have_valOutIso=false
):
When any primary pump is proven on, the bypass valve control loop is enabled.
The valve is opened 100 % otherwise.
When enabled, the bypass valve loop shall be biased to start with the valve 100 % open.