The HW minimum flow bypass valve is modulated based on a reverse acting control loop to maintain the primary HW flow rate at setpoint. The setpoint is calculated as described in Buildings.Templates.Plants.Controls.MinimumFlow.Setpoint using the number of units commanded on in heating mode at each stage.
When using isolation valve command signals
(have_valInlIso=true
or have_valOutIso=true
):
When any HW isolation valve is commanded open, the HW bypass valve control loop is enabled.
The valve is opened 100 % otherwise.
When enabled, the HW bypass valve loop shall be biased to start with the valve 100 % open.
Otherwise
(have_valInlIso=false
and have_valOutIso=false
):
The CHW minimum flow bypass valve is modulated based on a reverse acting control loop to maintain the primary CHW flow rate at setpoint. The setpoint is calculated as described in Buildings.Templates.Plants.Controls.MinimumFlow.Setpoint using the number of units commanded on in cooling mode at each stage.
When using isolation valve command signals
(have_valInlIso=true
or have_valOutIso=true
):
When any CHW isolation valve is commanded open, the CHW bypass valve control loop is enabled.
The valve is opened 100 % otherwise.
When enabled, the CHW bypass valve loop shall be biased to start with the valve 100 % open.
Otherwise
(have_valInlIso=false
and have_valOutIso=false
):