modelModeAlternation

Validation model for SHC and single mode alternation

Information

This model validates Buildings.Templates.Plants.Controls.PolyvalentHeatPumps.ModeAlternation in a configuration with two polyvalent heat pumps and a constant runtime order idxSor={1, 2}.

The number of units staged in each mode and the corresponding enable commands of each unit are varied over time to exercise both types of stage transition anticipated by this block.

  • Elementary single-mode staging, e.g., at t = 20 s and t = 40 s, unit 1 and then unit 2 are staged on in heating-only mode, and at t = 100 s, unit 1 is staged on in cooling-only mode.
  • A mode switch between a single mode and SHC mode, e.g., at t = 60 s, unit 2 switches from heating-only to SHC mode, and at t = 120 s, unit 1 switches from cooling-only to SHC mode.

Parameters

TypeNameDefaultDescription
IntegernPhp2Number of polyvalent units

Components

TypeNameDefaultDescription
Buildings.Templates.Plants.Controls.PolyvalentHeatPumps.ModeAlternationselModPhpMode alternation
Buildings.Controls.OBC.CDL.Integers.Sources.Constant[nPhp]idxSorRuntime order
Buildings.Controls.OBC.CDL.Integers.Sources.TimeTablenHeaNumber of units staged in heating mode
Buildings.Controls.OBC.CDL.Integers.Sources.TimeTablenCooNumber of units staged in cooling mode
Buildings.Controls.OBC.CDL.Integers.Sources.TimeTablenShcNumber of units staged in SHC mode
Buildings.Controls.OBC.CDL.Logical.Sources.TimeTableu1HeaEnable command in heating mode
Buildings.Controls.OBC.CDL.Logical.Sources.TimeTableu1CooEnable command in cooling mode
Buildings.Controls.OBC.CDL.Logical.Sources.TimeTableu1ShcEnable command in SHC mode