This model validates Buildings.Templates.Plants.Controls.Pumps.Generic.StagingHeadered with three plant equipment and three pumps and for the following configurations.
staPumPriDed
):
the number of pumps commanded on matches the number of operating
equipment with a one-to-one relationship.
staPumPriNoDp
):
the number of pumps commanded on matches the number of operating
equipment without a one-to-one relationship.
staPumPriDp
):
the number of pumps commanded on does not match the number of operating
equipment but is rather related to the fractional flow rate.
The simulation also exhibits the lead/lag rotation of the primary pumps.
staPumSecDp
):
the number of pumps commanded on does not match the number of operating
equipment but is rather related to the fractional flow rate.
All pumps are disabled when the plant is disabled.