When commanded on, the primary HW pumps are commanded at a fixed
speed yPumHeaWatPriSet, as determined during the
Testing, Adjusting, and Balancing phase to provide the design heat
pump flow.
When commanded on, the primary CHW pumps are commanded at a
fixed speed yPumChiWatPriSet, as determined during the
Testing, Adjusting, and Balancing phase to provide the design heat
pump flow.
When commanded on, the primary pumps are commanded at a fixed
speed yPumHeaWatPriSet in heating mode or
yPumChiWatPriSet in cooling mode, as determined during
the Testing, Adjusting, and Balancing phase to provide the design
heat pump flow in heating mode or cooling mode. The operating mode
of the associated heat pump is determined and latched at the time
the pump is enabled.
When commanded on, the primary HW pumps are commanded at a fixed
speed yPumHeaWatPriSet. When commanded on, the primary
CHW pumps are commanded at a fixed speed
yPumChiWatPriSet. The pump speed
yPumHeaWatPriSet or yPumChiWatPriSet is
determined during the Testing, Adjusting, and Balancing phase to
provide the design heat pump flow in heating mode or cooling
mode.
The pumps are controlled as described in Buildings.Templates.Plants.Controls.Pumps.Generic.ControlDifferentialPressure. The "pump proven on" condition is evaluated based on the primary HW pump status.
The pumps are controlled as described in Buildings.Templates.Plants.Controls.Pumps.Generic.ControlDifferentialPressure. The "pump proven on" condition is evaluated based on the primary CHW pump status.
The pumps are controlled as described in Buildings.Templates.Plants.Controls.Pumps.Generic.ControlDifferentialPressure. For the HW loop, the "pump proven on" condition is evaluated based on the status of the primary pumps associated with heat pumps that are commanded in heating mode. For the CHW loop, the "pump proven on" condition is evaluated based on the status of the primary pumps associated with heat pumps that are commanded in cooling mode. The operating mode of the associated heat pump is determined and latched at the time the pump is enabled.
The pumps are controlled as described in Buildings.Templates.Plants.Controls.Pumps.Generic.ControlDifferentialPressure. For the HW loop, the "pump proven on" condition is evaluated based on the status of the primary HW pumps. For the CHW loop, the "pump proven on" condition is evaluated based on the status of the primary CHW pumps.