When commanded on, the primary HW pumps are commanded at a fixed
speed yPumHeaWatPriSet
, as determined during the Testing, Adjusting,
and Balancing phase to provide the design heat pump flow.
When commanded on, the primary pumps are commanded at a fixed
speed yPumHeaWatPriSet
in heating mode or
yPumChiWatPriSet
in cooling mode, as determined during the
Testing, Adjusting, and Balancing phase to provide the design heat pump flow
in heating mode or cooling mode.
When commanded on, the primary HW pumps are commanded at a fixed
speed yPumHeaWatPriSet
.
When commanded on, the primary CHW pumps are commanded at a fixed
speed yPumChiWatPriSet
.
The pump speed yPumHeaWatPriSet
or yPumChiWatPriSet
is determined during the Testing, Adjusting, and Balancing phase to provide
the design heat pump flow in heating mode or cooling mode.