.Buildings.Templates.Plants.Controls.Setpoints.PlantReset

Plant reset logic

Information

This logic is used in primary-only and primary-secondary systems serving differential pressure controlled pumps.

CHW loops with differential pressure control

The CHW supply temperature setpoint and pump differential pressure setpoint are reset based on the current value of the logic variable called "CHW Plant Reset" as shown below and described subsequently.

CHW plant reset logic diagram

HW loops with differential pressure control

The HW supply temperature setpoint and pump differential pressure setpoint are reset based on the current value of the logic variable called "HW Plant Reset" as shown below and described subsequently.

CHW plant reset logic diagram

Generic reset logic applicable to all plants

From 0 % loop output to resDp_max loop output, reset differential pressure setpoint from dpSet_min to dpSet_max.

From resTSup_min loop output to 100 % loop output, reset supply temperature setpoint from TSupSetLim to TSup_nominal.

CHW/HW Plant Reset variable is reset using trim and respond logic with the following parameters:

Variable Value Definition
DeviceAny pump distribution loop Associated device
SP0res_initInitial reset value
SPminres_minMinimum reset value
SPmaxres_maxMaximum reset value
TddtDelDelay time before the reset begins
TdtResTime step
InReqResIgnNumber of ignored requests
RnReqResNumber of requests
SPtrimtriTrim amount
SPresrspRespond amount
SPres_maxrsp_maxMaximum response per time interval

The plant reset loop is enabled when the plant is enabled and disabled when the plant is disabled.

When a plant stage change is initiated, the plant reset logic is disabled and value fixed at its last value for the longer of dtHol and the time it takes for the plant to successfully stage.

Plants serving more than one set of differential pressure controlled pumps

A unique instance of the above reset is used for each set of differential pressure controlled pumps.

Plants where more than one remote ∆p sensor serves a given set of primary or secondary pumps ∆p

Where more than one remote ∆p sensor serves a given set of primary or secondary pumps, remote ∆p setpoints for all remote sensors serving those pumps shall increase in unison. Note: if remote sensors have different dpSet_max values, then the amount each ∆p setpoint changes per percent loop output will differ.

Revisions


Generated at 2025-04-19T18:20:10Z by OpenModelicaOpenModelica 1.25.0 using GenerateDoc.mos