If a heat pump is commanded on in a desired heating or cooling mode:
-
The isolation valves for desired heating or cooling mode are commanded
open.
-
Plants with dedicated primary pumps:
The dedicated primary pumps are commanded on when the
associated isolation valves are commanded open.
-
Plants with headered primary pumps:
The headered primary pumps are commanded on as described in
Buildings.Templates.Plants.Controls.Pumps.Generic.StagingHeadered.
-
Once the isolation valves are fully open (based on nominal valve timing
dtVal
)
and the lead pumps are proven on, the heat pump is enabled in heating or cooling
mode.
If a heat pump is commanded off:
-
The heat pump is disabled.
-
After the time required for the internal shutdown cycle to time out
(
dtOff
to be determined empirically, defaulting to 3 min),
all isolation valves are commanded closed.
-
Plants with dedicated primary pumps:
The dedicated primary pumps are commanded off when the associated
isolation valves are commanded closed.
-
Plants with headered primary pumps:
The headered primary pumps are commanded off as described in
Buildings.Templates.Plants.Controls.Pumps.Generic.StagingHeadered.
-
March 29, 2024, by Antoine Gautier:
First implementation.