For heating applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
dT for a period of dtSec
and secondary HW supply temperature < setpoint – dT
for dtSec.dT
for dtPri.For heating applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
dT
for dtPri.For cooling applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
dT for a period of dtSec
and secondary CHW supply temperature < setpoint +
dT for dtSec.dT
for dtPri.For cooling applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
dT
for dtPri.