For heating applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
dT
for a period of dtSec and secondary HW supply temperature
< setpoint – dT for dtSec.
dT for
dtPri.
For heating applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
dT for
dtPri.
For cooling applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
dT
for a period of dtSec and secondary CHW supply temperature
< setpoint + dT for dtSec.
dT for
dtPri.
For cooling applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
dT for
dtPri.