This class implements the sequence of operation for plants with air-to-water heat pumps. It is based on the controller Buildings.Templates.Plants.Controls.HeatPumps.AirToWater.
The control sequence requires the following external input points in addition to those already included in the HP plant template.
TOut:
AI signal with a dimensionality of zerodpHeaWatRem:
AI signal with a dimensionality of one, the number of remote
sensors is specified by the parameter nSenDpHeaWatRem.dpChiWatRem – 
only for heating and cooling plants:
AI signal with a dimensionality of one, the number of remote
sensors is specified by the parameter nSenDpChiWatRem.busAirHan[:] or busEquZon[:],
with a dimensionality of one
bus(AirHan|EquZon)[:].reqPlaHeaWat:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqResHeaWat:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqPlaChiWat:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqResChiWat:
AI signal (Integer), with a dimensionality of one