This class implements the sequence of operation for plants with air-to-water heat pumps. It is based on the controller Buildings.Templates.Plants.Controls.HeatPumps.AirToWater.
The control sequence requires the following external input points in addition to those already included in the HP plant template.
TOut
:
AI signal with a dimensionality of zerodpHeaWatRem
:
AI signal with a dimensionality of one, the number of remote
sensors is specified by the parameter nSenDpHeaWatRem
.dpChiWatRem
–
only for heating and cooling plants:
AI signal with a dimensionality of one, the number of remote
sensors is specified by the parameter nSenDpChiWatRem
.busAirHan[:]
or busEquZon[:]
,
with a dimensionality of one
bus(AirHan|EquZon)[:].reqPlaHeaWat
:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqResHeaWat
:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqPlaChiWat
:
AI signal (Integer), with a dimensionality of one
bus(AirHan|EquZon)[:].reqResChiWat
:
AI signal (Integer), with a dimensionality of one