This model is used for the test case 650 of the BESTEST validation suite.
Case650 is the same as Case600, but with the following modifications:
-
From 1800 hours to 0700 hours, vent fan = on
-
From 0700 hours to 1800 hours, vent fan = off
-
Heating is always off
-
From 0700 hours to 1800 hours, cooling is on if zone temperature > 27°C,
otherwise cool = off.
-
From 1800 hours to 0700 hours, cooling is always off.
-
Ventilation fan capacity is 1700 standard m3/h (in addition to specified
infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
-
No waste heat from fan.
-
May 12, 2023, by Jianjun Hu:
Added test acceptance criteria limits.
This is for
issue 3396.
-
May 12, 2022, by Jianjun Hu:
Changed the ventilation fan capacity from 1703.16 m3/h to 1700 m3/h and consider the adjustment
for the altitude, eventually to be 1409 m3/h.
This is for #3005.
-
July 15, 2012, by Michael Wetter:
Revised implementation to extend from base case to avoid duplicate code.
Merged model into the Buildings library.
-
June 5, 2012, by Vladimir Vukovic:
First implementation.