modelASHRAE2006Summer_Autosizing

Variable air volume flow system with terminal reheat and five thermal zones using a control sequence published by ASHRAE in 2006 with HVAC sized using autosizing

Extends from Buildings.ThermalZones.EnergyPlus_24_2_0.Examples.SmallOffice.ASHRAE2006Winter_Autosizing (Variable air volume flow system with terminal reheat and five thermal zones using a control sequence published by ASHRAE in 2006 with HVAC sized using autosizing).

Information

This is the same model as Buildings.ThermalZones.EnergyPlus_24_2_0.Examples.SmallOffice.ASHRAE2006Winter_Autosizing but configured for simulation of a few days in summer.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.VolumeVRooCor (from HVACBuilding)flo.VRooCorRoom volume corridor
Modelica.Units.SI.VolumeVRooSou (from HVACBuilding)flo.VRooSouRoom volume south
Modelica.Units.SI.VolumeVRooNor (from HVACBuilding)flo.VRooNorRoom volume north
Modelica.Units.SI.VolumeVRooEas (from HVACBuilding)flo.VRooEasRoom volume east
Modelica.Units.SI.VolumeVRooWes (from HVACBuilding)flo.VRooWesRoom volume west
Modelica.Units.SI.AreaAFloCor (from HVACBuilding)flo.AFloCorFloor area corridor
Modelica.Units.SI.AreaAFloSou (from HVACBuilding)flo.AFloSouFloor area south
Modelica.Units.SI.AreaAFloNor (from HVACBuilding)flo.AFloNorFloor area north
Modelica.Units.SI.AreaAFloEas (from HVACBuilding)flo.AFloEasFloor area east
Modelica.Units.SI.AreaAFloWes (from HVACBuilding)flo.AFloWesFloor area west
Realconv (from HVACBuilding)1.2/3600Conversion factor for nominal mass flow rate
Modelica.Units.SI.MassFlowRatemCor_flow_nominal (from HVACBuilding)Design mass flow rate core
Modelica.Units.SI.MassFlowRatemSou_flow_nominal (from HVACBuilding)Design mass flow rate south
Modelica.Units.SI.MassFlowRatemEas_flow_nominal (from HVACBuilding)Design mass flow rate east
Modelica.Units.SI.MassFlowRatemNor_flow_nominal (from HVACBuilding)Design mass flow rate north
Modelica.Units.SI.MassFlowRatemWes_flow_nominal (from HVACBuilding)Design mass flow rate west
Modelica.Units.SI.MassFlowRate[5]mCooVAV_flow_nominal (from HVACBuilding){mSou_flow_nominal, mEas_flow_nominal, mNor_flow_nominal, mWes_flow_nominal, mCor_flow_nominal}Design mass flow rate of each zone
Modelica.Units.SI.TemperatureTHeaWatInl_nominal (from HVACBuilding)45 + 273.15Reheat coil nominal inlet water temperature
Modelica.Units.SI.TemperatureTZonSetAve (from ASHRAE2006Winter_Autosizing)(mCor_flow_nominal*flo.cor.sizCoo.TSet + mSou_flow_nominal*flo.sou.sizCoo.TSet + mEas_flow_nominal*flo.eas.sizCoo.TSet + mNor_flow_nominal*flo.nor.sizCoo.TSet + mWes_flow_nominal*flo.wes.sizCoo.TSet)/(mCor_flow_nominal + mSou_flow_nominal + mEas_flow_nominal + mNor_flow_nominal + mWes_flow_nominal)Average cooling zone temperature set point weighted by zone airflow
Modelica.Units.SI.MassFractionXZonSetAve (from ASHRAE2006Winter_Autosizing)(mCor_flow_nominal*flo.cor.sizCoo.XSet + mSou_flow_nominal*flo.sou.sizCoo.XSet + mEas_flow_nominal*flo.eas.sizCoo.XSet + mNor_flow_nominal*flo.nor.sizCoo.XSet + mWes_flow_nominal*flo.wes.sizCoo.XSet)/(mCor_flow_nominal + mSou_flow_nominal + mEas_flow_nominal + mNor_flow_nominal + mWes_flow_nominal)Average cooling zone humidity ratio cooling set point weighted by zone airflow
Modelica.Units.SI.TemperatureTCooAirSup_nominal (from ASHRAE2006Winter_Autosizing)12 + 273.15Nominal discharge air temperature for AHU during cooling
Modelica.Units.SI.MassFractionXCooAirSup_nominal (from ASHRAE2006Winter_Autosizing)0.0085/(1 + 0.0085)Nominal discharge air humidity ratio for AHU during cooling
Modelica.Units.SI.HeatFlowRateQCooSenAHU_flow_nominal (from ASHRAE2006Winter_Autosizing)hvac.mCooAir_flow_nominal*cpAir*(TCooAirSup_nominal - hvac.TCooAirMix_nominal)Nominal sensible cooling load on AHU cooling coil
Modelica.Units.SI.HeatFlowRateQCooLatAHU_flow_nominal (from ASHRAE2006Winter_Autosizing)hvac.mCooAir_flow_nominal*h_fg*(XCooAirSup_nominal - hvac.wCooAirMix_nominal)Nominal latent cooling load on AHU cooling coil
Modelica.Units.SI.TemperatureTHeaAirDis_nominal (from ASHRAE2006Winter_Autosizing)40 + 273.15Nominal discharge air temperature for VAV boxes during heating
Modelica.Units.SI.SpecificHeatCapacitycpAir (from ASHRAE2006Winter_Autosizing)MediumA.specificHeatCapacityCp(state_default)Specific heat capacity of air at default medium state
Modelica.Units.SI.SpecificEnergyh_fg (from ASHRAE2006Winter_Autosizing)MediumA.enthalpyOfCondensingGas(TCooAirSup_nominal)Latent heat of water vapor

Components

TypeNameDefaultDescription
Buildings.Examples.VAVReheat.BaseClasses.PartialHVAChvac (from HVACBuilding)
Buildings.Examples.VAVReheat.BaseClasses.PartialFloorflo (from HVACBuilding)
Buildings.BoundaryConditions.WeatherData.ReaderTMY3weaDat (from HVACBuilding)Weather data reader
Fluid.Sources.Boundary_pTsinHea (from HVACBuilding)Sink for heating coil
Fluid.Sources.Boundary_pTsouHea (from HVACBuilding)Source for heating coil
Fluid.Sources.Boundary_pTsinCoo (from HVACBuilding)Sink for cooling coil
Fluid.Sources.Boundary_pTsouCoo (from HVACBuilding)Source for cooling coil loop
Fluid.Sources.Boundary_pTsouHeaTer (from HVACBuilding)Source for heating of terminal boxes
Fluid.Sources.Boundary_pTsinHeaTer (from HVACBuilding)Source for heating of terminal boxes

Revisions

  • July 23, 2026, by David Blum:
    First implementation.