Case 900, but with heating schedule
This model is used for the basic test case 940 of the BESTEST
validation suite. Case940 is the same as Case900, but with the
following modifications:
- From 23h00 hours to 07h00 hours, heat = on if zone temperature
is below 10°C
- From 07h00 hours to 08h00 hours, the thermostat setpoint shall
vary linearly with time from 10 °C to 20 °C. If the zone
temperature is less than the thermostat setpoint for a subhourly
time step, heat shall be added to the zone such that the zone
temperature at the end of each subhourly time step shall correspond
to the thermostat setpoint that occurs at the end of each subhourly
time step.
- From 08h00 hours to 23h00 hours, heat = on if zone temperature
is below 20°C
- All hours, cool = on if zone temperature above 27°C
- Otherwise, mechanical equipment is off.
- Mar 2, 2024, by Alessandro Maccarini:
First implementation.
Generated at 2026-04-05T18:18:26Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos