modelPartialChillerWSEInterface

Partial model that defines the interface for chiller and WSE package

Extends from Buildings.Fluid.Interfaces.PartialFourPort (Partial model with four ports).

Information

This model implements an interface for chillers and integrated/nonitegrated water-side economizers.

Parameters

TypeNameDefaultDescription
Integernum2Total number of chillers and waterside economizer
Assumptions
BooleanallowFlowReversal1 (from PartialFourPort)true= false to simplify equations, assuming, but not enforcing, no flow reversal for medium 1
BooleanallowFlowReversal2 (from PartialFourPort)true= false to simplify equations, assuming, but not enforcing, no flow reversal for medium 2
Chiller
Modelica.Units.SI.MassFlowRatem1_flow_chi_nominalNominal mass flow rate on the medium 1 side in the chiller
Modelica.Units.SI.MassFlowRatem2_flow_chi_nominalNominal mass flow rate on the medium 2 side in the chiller
Waterside economizer
Modelica.Units.SI.MassFlowRatem1_flow_wse_nominalNominal mass flow rate on the medium 1 side in the waterside economizer
Modelica.Units.SI.MassFlowRatem2_flow_wse_nominalNominal mass flow rate on the medium 2 side in the waterside economizer
Advanced
Medium1.MassFlowRatem1_flow_small1E-4*abs(m1_flow_chi_nominal)Small mass flow rate for regularization of zero flow
Medium2.MassFlowRatem2_flow_small1E-4*abs(m2_flow_chi_nominal)Small mass flow rate for regularization of zero flow
Advanced › Diagnostics
Booleanshow_Tfalse= true, if actual temperature at port is computed

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_a1 (from PartialFourPort)Fluid connector a1 (positive design flow direction is from port_a1 to port_b1)
Modelica.Fluid.Interfaces.FluidPort_bport_b1 (from PartialFourPort)Fluid connector b1 (positive design flow direction is from port_a1 to port_b1)
Modelica.Fluid.Interfaces.FluidPort_aport_a2 (from PartialFourPort)Fluid connector a2 (positive design flow direction is from port_a2 to port_b2)
Modelica.Fluid.Interfaces.FluidPort_bport_b2 (from PartialFourPort)Fluid connector b2 (positive design flow direction is from port_a2 to port_b2)
Modelica.Blocks.Interfaces.RealInputTSetSet point for leaving water temperature
Modelica.Blocks.Interfaces.BooleanInput[num]onSet to true to enable equipment, or false to disable equipment

Components

TypeNameDefaultDescription
Medium1.MassFlowRatem1_flowport_a1.m_flowMass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction)
Modelica.Units.SI.PressureDifferencedp1port_a1.p - port_b1.pPressure difference between port_a1 and port_b1
Medium2.MassFlowRatem2_flowport_a2.m_flowMass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction)
Modelica.Units.SI.PressureDifferencedp2port_a2.p - port_b2.pPressure difference between port_a2 and port_b2
Medium1.ThermodynamicStatesta_a1Medium1.setState_phX(port_a1.p, noEvent(actualStream(port_a1.h_outflow)), noEvent(actualStream(port_a1.Xi_outflow)))Medium properties in port_a1
Medium1.ThermodynamicStatesta_b1Medium1.setState_phX(port_b1.p, noEvent(actualStream(port_b1.h_outflow)), noEvent(actualStream(port_b1.Xi_outflow)))Medium properties in port_b1
Medium2.ThermodynamicStatesta_a2Medium2.setState_phX(port_a2.p, noEvent(actualStream(port_a2.h_outflow)), noEvent(actualStream(port_a2.Xi_outflow)))Medium properties in port_a2
Medium2.ThermodynamicStatesta_b2Medium2.setState_phX(port_b2.p, noEvent(actualStream(port_b2.h_outflow)), noEvent(actualStream(port_b2.Xi_outflow)))Medium properties in port_b2

Revisions

  • June 30, 2017, by Yangyang Fu:
    First implementation.