modelWatersideEconomizer

Validate model Buildings.Applications.DataCenters.ChillerCooled.Equipment.WatersideEconomizer

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

This example demonstrates that the temperature at port_b2 is controlled by setting use_controller=true.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.MassFlowRatemCHW_flow_nominal2567.1*1000/(4200*10)Nominal mass flow rate at chilled water
Modelica.Units.SI.MassFlowRatemCW_flow_nominal2567.1*1000/(4200*8.5)Nominal mass flow rate at condenser water
Modelica.Units.SI.PressureDifferencedpCHW_nominal40000Nominal pressure
Modelica.Units.SI.PressureDifferencedpCW_nominal40000Nominal pressure
IntegernumChi1Number of chillers

Components

TypeNameDefaultDescription
Buildings.Applications.DataCenters.ChillerCooled.Equipment.WatersideEconomizerWSEWaterside economizer
Buildings.Fluid.Sources.MassFlowSource_Tsou2Source on medium 2 side
Buildings.Fluid.Sources.Boundary_pTsin1Sink on medium 1 side
Buildings.Fluid.Sources.MassFlowSource_Tsou1Source on medium 1 side
Modelica.Blocks.Sources.TimeTableTCon_inCondenser inlet temperature
Buildings.Fluid.Sources.Boundary_pTsin2Sink on medium 2 side
Modelica.Blocks.Sources.ConstantTEva_inEvaporator inlet temperature
Modelica.Blocks.Sources.ConstantTSetLeaving chilled water temperature setpoint
Buildings.Fluid.Sensors.TemperatureTwoPortTSupTemperature sensor
Modelica.Blocks.Sources.BooleanSteponWSEOn and off signal for the WSE

Contents

NameDescription
MediumCHWMedium model
MediumCWMedium model

Revisions

  • September 11, 2017, by Michael Wetter:
    Corrected wrong use of replaceable model in the base class.
    This is for issue 921.
  • July 10, 2017, by Yangyang Fu:
    First implementation.