modelSeparateWithDP

Validation model for the minimum outdoor air control - damper position limits for the units with separated outdoor air control

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithDP for the following control signals: VOut_flow, VOutMinSet_flow.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithDPdisMinConDisable the minimum outdoor air control due to that the supply fan is not proven on
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithDPdisMinCon1Disable the minimum outdoor air control due to that it is not in occupied mode
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithDPminConMulti zone VAV AHU minimum outdoor air control - damper position limits
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVOutMinSet_flowOutdoor volumetric airflow rate setpoint, 15cfm/occupant and 100 occupants

Revisions

  • February 5, 2022, by Jianjun Hu:
    First implementation.